IS230STTCH2A GE Module Parts Simplex Thermocouple Input Terminal Board
The GE IS230STTCH2A is a Simplex Thermocouple Input Terminal Board designed for General Electric's Mark VIe turbine control system. It provides an interface for connecting field thermocouples to the system's thermocouple input processing module.
The terminal board supports up to 12 thermocouple input channels and provides signal conditioning, noise filtering, and cold-junction reference functionality to ensure reliable temperature measurement.
The IS230STTCH2A works with compatible PTCC I/O packs in Mark VIe systems. It is commonly used in gas turbine temperature monitoring, combustion control, and industrial process temperature measurement.
| Parameter | Specification |
|---|---|
| Manufacturer | General Electric (GE) |
| Model | IS230STTCH2A |
| Product Type | Thermocouple Input Terminal Board |
| Product Series | Mark VIe |
| System Configuration | Simplex |
| Number of Channels | 12 |
| Input Signal | Thermocouple / Millivolt |
| Supported Thermocouples | E, J, K, S, T |
| Extended Compatibility | B, N, R (depending on I/O pack) |
| Compatible I/O Pack | PTCC series |
| Cold Junction Compensation | Integrated |
| Signal Conditioning | Built-in filtering |
| Communication Interface | DC-37 connector to I/O pack |
| Mounting | DIN-Rail or Panel Mount |
| Terminal Type | Euro-block terminal |
| Application | Gas Turbine Control |
- Thermocouple Signal Acquisition: Collects temperature signals from up to 12 thermocouple sensors.
- Signal Conditioning: Filters electrical noise and stabilizes weak millivolt signals.
- Cold Junction Compensation: Provides a reference temperature signal for accurate thermocouple measurement.
- Signal Transmission: Transfers acquired signals to the compatible thermocouple I/O processor.
- Equipment Identification: Uses an onboard identification chip for system recognition and diagnostics.
- Gas turbine exhaust temperature monitoring.
- Combustion chamber temperature measurement.
- Industrial boiler temperature monitoring.
- Power generation control systems.
- Industrial process temperature monitoring.
- Turbine auxiliary equipment monitoring.
- 12-channel thermocouple input capability.
- Reliable temperature signal acquisition.
- Integrated signal conditioning and filtering.
- Supports multiple thermocouple types.
- Compact DIN-rail mounting design.
- Compatible with GE Mark VIe control architecture.
- Designed for continuous industrial operation.
It is a Simplex Thermocouple Input Terminal Board used in GE Mark VIe turbine control systems for temperature signal acquisition.
It supports 12 thermocouple input channels.
Common supported types include E, J, K, S, and T. Additional types may be available depending on the connected I/O pack.
Yes. It is designed for integration with the GE Mark VIe control platform through compatible thermocouple I/O packs.
It is a Simplex terminal board and is intended for simplex applications rather than TMR configurations.
GE Simplex Thermocouple Input Board
,IS230STTCH2A Thermocouple Terminal Board
,GE Module Parts Thermocouple Board
-
IS220PVIBH1A 336A4940CSP16 Vibration Monitoring I/O Pack
GE IS220PVIBH1A (336A4940CSP16) Vibration Monitoring I/O Pack for Mark VIe systems. Features 13 differential channels, dual Ethernet, and -30 to 65°C operation. Supports Proximitor, Velomitor, and seismic sensors. Reliable turbine protection with 1-year warranty. -
IS230STAOH2A GE Module Parts Analog Output Terminal Board
The GE IS230STAOH2A Analog Output Terminal Board offers 8 channels with 0-20 mA output for Mark VIe systems. It features plug-and-play DIN rail mounting, surge suppression, and operates reliably from -20°C to 85°C, ensuring precise control of valves and actuators in demanding industrial environments. -
IS230TNPAH2A GE Module Parts Primary Trip DIN-Rail Module
GE IS230TNPAH2A Primary Trip DIN-Rail Module for Mark VIe turbine control. Ensures reliable emergency shutdown with 2500V insulation, 15A rating, and -40°C to 85°C range. USA-made, 1-year warranty. Ideal for power plants and industrial energy installations.