PM866A-2 3BSE050201R1 ABB Full Redundant CPU Module | Original AC 800M Controller In Stock

Product Summary
ABB PM866A-2 full redundant CPU module for AC 800M DCS. Features <10ms failover, 32-bit RISC, 64MB SRAM, dual Ethernet/serial ports, DIN rail mount, IP20, 12-month warranty. In stock, fast global shipping.
Product Description
ABB PM866A-2 3BSE050201R1 Full Redundant CPU Module

The ABB PM866A-2 (Part Number: 3BSE050201R1) is a high-performance, full redundant Central Processing Unit (CPU) module in the AC 800M controller family. Designed specifically for distributed control systems (DCS) such as ABB 800xA and Freelance, it serves as the core processing unit for complex process control, data acquisition, and equipment linkage.
Unlike standard single-CPU controllers, the PM866A-2 is engineered for mission-critical applications requiring absolute reliability. It implements comprehensive redundancy across the CPU, CEX-Bus, communication interfaces, and S800 I/O. When a primary controller fails, the backup takes over in under 10 milliseconds without interrupting active control logic, making it the ultimate choice for continuous production lines in petrochemical, power generation, and heavy manufacturing plants.

Technical Specifications
ManufacturerABB
Model / Part NumberPM866A-2 / 3BSE050201R1
Product TypeFull Redundant Process Controller Module (CPU)
Processor32-bit RISC architecture
Memory64 MB SRAM + 16 MB Non-volatile Flash
Communication2 x RJ45 Ethernet ports (CN1, CN2), 2 x RS232 serial ports
Redundancy SupportFull redundancy: CPU, CEX-Bus, Communication, and S800 I/O
Failover Time< 10 ms (Seamless switchover without interrupting control logic)
InstallationStandard DIN rail sliding and locking installation
Protection ClassIP20
Operating Temperature0°C to +60°C
Dimensions130 mm × 85 mm × 25 mm
WeightApprox. 0.4 kg
ConditionBrand New & In Stock
Warranty12 Months
Key Features & Benefits
  • Ultimate Full Redundancy Architecture: The PM866A-2 is designed as a full redundant master control unit for DCS systems. It eliminates the need for additional hardware switching units by natively supporting redundant CPU, CEX-Bus, communication interfaces, and S800 I/O. This ensures that if the primary hardware fails, the backup side takes over seamlessly in milliseconds, preventing catastrophic production halts.
  • High-Performance Processing: Equipped with a robust 32-bit RISC processor and 64 MB of SRAM, it effortlessly handles complex control algorithms, large application programs, and high-speed data processing tasks required by modern industrial automation.
  • Robust Environmental Adaptability: With an operating temperature range up to +60°C and an IP20 protection class, it is built to withstand harsh industrial environments, such as power plant DCS cabinets where internal temperatures can consistently exceed 55°C during summer.
  • Extensive I/O & Communication Capacity: Supports CEX-bus expansion, allowing connection to numerous I/O stations and communication modules. It features dual Ethernet ports for control network connectivity and dual serial ports for configuration and modem control.
Compatible & Related Modules

To build a complete AC 800M full redundant system, the PM866A-2 is frequently paired with the following components:

Installation & Maintenance Guidelines
Pre-Installation Preparation

Before installing the PM866A-2 3BSE050201R1, ensure the control cabinet is free of dust and oil. Maintain at least 10 cm of clearance from heat-generating components for proper ventilation. Verify the 24V DC power supply voltage and check communication cable connectors for oxidation. If configuring redundancy, ensure both the main and backup modules are securely mounted on their respective TP830 baseplates with the CEX-Bus and RCU-Link cables properly connected.

Routine Maintenance
  • Weekly: Check the LED indicator status on both CPUs. Solid green lights indicate normal operation and successful synchronization; flashing lights require immediate communication troubleshooting.
  • Monthly: Wipe the module surface with a dry cloth to prevent dust accumulation and static buildup.
  • Quarterly: Back up program data from the non-volatile Flash memory to prevent accidental loss. Check the status of the memory backup batteries and replace if necessary.
  • Troubleshooting: If fault codes appear, use ABB 800xA Control Builder diagnostic software to read the fault logs and pinpoint the issue rather than disassembling the hardware.
Why Choose Us for Your ABB Spare Parts?
  • Fast Global Delivery: In-stock items are typically shipped within 2 days, with expedited global delivery options (3–5 working days) available.
  • Quality Assurance: All products are 100% original and come with a 12-month warranty. We guarantee reliable performance for your industrial control systems.
  • Expert Support: Our seasoned technical team provides 7×12 hours support for installation, communication integration, and troubleshooting.
ABB PM866A-2 3BSE050201R1 full redundant CPU module for AC 800M controller, product reference image

Request a Quote

Can't find a specific part? Contact us today for a personalized quote on the ABB PM866A-2 3BSE050201R1 or other automation spare parts.

Product Details
Highlight:

ABB PM866A-2 redundant CPU module

,

ABB AC 800M controller module

,

ABB original module in stock

Type: Electrical Module Components
Currentrating: Up To 100A
Operating Temperature: -40 ~150C
Protectionrating: IP20 To IP65 Depending On Model
Mounting Type: DIN Rail Mountable
Standardscompliance: IEC 60947
Warranty: 1 Years Manufacturer Warranty
Thermalresistance: 0.2 K/W

Miss. Liliya

Related Products
Send An Inquiry